Standard operating procedure to operate the high tension panel.

1.0 OBJECTIVE

To lay down the procedure for operation of high tension (H.T.) panel.

2.0 SCOPE

This SOP shall be applicable for H.T.

3.0 RESPONSIBILITY

Operator/ Officer

4.0 ACCOUNTABILITY

HOD Engineering

5.0 PROCEDURE

5.1 For Putting ON the Panel

5.1.1 Ensure breaker in its position inside the panel.
5.1.2 Ensure that “TRIP CIRCUIT HEALTHY” indication appears on the panel.
5.1.3 Check incoming voltage between R-Y, Y-B & B-R on the voltmeter provided, it should be 10.5 to 11KV.
5.1.4 Close the breaker by turning the rotary switch to “CLOSE” position.
5.1.5 Ensure vacuum circuit breaker is in ON position.
5.1.6 Following indication lamps will glow.
i) BREAKER ON, ii) TRIP CIRCUIT HEALTHY, iii) SPRING CHARGED & iv) SERVICE POSITION.
5.1.7 Close Vacuum Circuit Breaker of transformer 1 by turning rotary switch to CLOSE POSITION.
5.1.8 Close Vacuum Circuit Breaker of Transformer-2 by turning rotary switch to CLOSE POSITION.

5.2 For Putting OFF the Panel

5.2.1 Trip the vacuum circuit breaker of transformer-1 by turning the rotary switch to “TRIP” position.
5.2.2 Breaker will trip and transformer -1will be put OFF.
5.2.3 Trip Incomer circuit breaker of the transformer -2 by turning the rotary switch to TRIP position.
5.2.4 Breaker will trip and transformer-2 will be put OFF.
5.2.5 Trip incomer vacuum circuit breaker by turning the rotary switch to trip position. Entire panel will OFF.

5.3 For Drawing out the Breaker

5.3.1 Trip the circuit breaker, which is to be drawn out.
5.3.2 Open the front door.
5.3.3 Remove the metallic plug of control wires from its socket.
5.3.4 Unlock the break by shifting a pin on the right side adjacent to plug.
5.3.5 Draw out the breaker trolley with the help of special key provided.

5.4 For drawing in the breaker

5.4.1 Push the breaker trolley inside as you have taken out.
5.4.2 Lock the pin, which was used to unlock it.
5.4.3 Put the metallic plug of control wires into its socket.
5.4.4 Close the door of the breaker panel.
5.4.5 Breaker is ready to be put on.
Related: SOP for Operation and Maintenance of Low Tension (L.T.) Panels

6.0 ABBREVIATION

6.1 SOP: Standard Operating Procedure
Get ready to use editable documents in MS-Word FormatView List





Ankur Choudhary is India's first professional pharmaceutical blogger, author and founder of pharmaguideline.com, a widely-read pharmaceutical blog since 2008. Sign-up for the free email updates for your daily dose of pharmaceutical tips.
.moc.enilediugamrahp@ofni :liamENeed Help: Ask Question


No comments:

Post a Comment

Please don't spam. Comments having links would not be published.


Popular Categories

QA SOPs QC SOPs Micro SOPs HVAC Production SOPs Stores SOPs Checklists Maintenance SOPs HPLC Sterile GLP Validation Protocols Water System GDP Regulatory Maintenance Calibration Warning Letters Education B.Pharmacy
Online Courses


Follow Pharmaguideline


DOCUMENTS

PHARMACEUTICAL DOCUMENTS




Editable Pharmaceutical Documents in MS-Word Format. Ready to use SOPs, Protocols, Master Plans, Manuals and more...

View


adsbypg


Recent Posts