SOP for Measurement of Air Velocity and Calculation of Air Changes per Hour for Classified Areas

Standard operating procedure to measure the air velocity and air changes per hour in CFM in classified area.

1.0 OBJECTIVE

To lay down the procedure for measurement of air velocity and calculation of air changes per hour for classified areas.

2.0 SCOPE

This SOP shall be applicable for classified areas and laminar air flow.

3.0 RESPONSIBILITY

Officer /Executive/ Assistant Manager

4.0 ACCOUNTABILITY

HOD engineering

5.0 PROCEDURE

5.1 Ensure that air handling unit is ON of that area.
5.2 Measure the hood /grill size and calculate the area of the hood/ grill in sqft.
5.3 In case of terminal HEPA filters place the calibrated anemometer 6 inches away from the grill at different locations and measure the air velocity in feet per minute.
5.4 In case of diffusers place the calibrated anemometer at the bottom face of the hood at different locations and measure the air velocity in feet per minute.
5.5 Calculate the average air velocity of the five locations.
5.6 Calculate the air quantity in CFM by multiplying the area with average air velocity.
5.7 Repeat the Step 5.2 to step 5.5 for all supply air diffusers/ grills available in the room.
5.8 Calculate the total air quantity in CFM inside the room.
5.9 Calculate the air changes per hour.
5.10 Record the observations in a format of measurement of air velocity and calculation of air changes.
5.11 The frequency for measurement of air velocity and calculation of air changes shall be once in a year for classified areas.
5.12 The frequency for measurement of air velocity for laminar air flow shall be once in six months and shall be done by an external agency.
5.12.1 The velocity measurement shall be carried out as per schedule.

5.13 Acceptance Criteria

5.13.1 The measured air quantity shall not be less than the designed air quantity and the calculated air changes shall not be less than the designed air changes per hour.
5.13.2 Average air velocity for laminar air flow shall be 90 + 20%.
5.14 If the acceptance criteria do not meet then take the necessary corrective actions and repeat the step 5.3 to step 5.9.

6.0 ABBREVIATIONS

6.1 SOP: Standard Operating Procedure
6.2 HEPA: High Efficiency Particulate Air
Get ready to use editable documents in MS-Word FormatView List





Ankur Choudhary is India's first professional pharmaceutical blogger, author and founder of pharmaguideline.com, a widely-read pharmaceutical blog since 2008. Sign-up for the free email updates for your daily dose of pharmaceutical tips.
.moc.enilediugamrahp@ofni :liamENeed Help: Ask Question


No comments:

Post a Comment

Please don't spam. Comments having links would not be published.


Popular Categories

QA SOPs QC SOPs Micro SOPs HVAC Production SOPs Stores SOPs Checklists Maintenance SOPs HPLC Sterile GLP Validation Protocols Water System GDP Regulatory Maintenance Calibration Warning Letters Education B.Pharmacy
Online Courses


Follow Pharmaguideline


DOCUMENTS

PHARMACEUTICAL DOCUMENTS




Editable Pharmaceutical Documents in MS-Word Format. Ready to use SOPs, Protocols, Master Plans, Manuals and more...

View


adsbypg


Recent Posts