SOP for Carrying Out Air Borne Particle Count in Static Condition : Pharmaguideline

Online GMP Courses with Certificate

ENROLL

SOP for Carrying Out Air Borne Particle Count in Static Condition

Standard operating procedure to count non viable particles in classified area using particle counter.

1.0 OBJECTIVE

To lay down the procedure for carrying out airborne particle count in the static condition.

2.0 SCOPE

This SOP shall be applicable for clean rooms, corridors, laminar air flow and process equipment.

3.0 RESPONSIBILITY

Officer /Executive/ Assistant Manager

4.0 ACCOUNTABILITY

HOD engineering

5.0 PROCEDURE

5.1 Ensure that the area is cleaned and air handling unit is kept ON for at least two hours before taking particle count.
5.2 The particle count to be performed by an outside agency.
5.3 Ensure that the particle counter used is duly calibrated and the certificate for the same must be traceable to national/ international standards.
5.4 Sample 1 cubic feet of air per minute under normalized mode.
5.5 Calculation for the number of locations for particle count
5.5.1 Number of sample locations shall be taken as the square root of the area in meter square of clean room/zone.
5.5.2 This number shall be rounded up to a nearest higher number.
5.5.3 If the number of location is one then minimum three samples shall be taken at that location.
5.6 The locations for taking the samples shall be near doors, return air raisers, at corners and near equipment.
5.7 The count shall be always taken for 1 minute and at working height of about 1 meters from the ground level.
5.8 After completion of the particle count in a particular room/ zone take the printout.
5.9.1 The particle count for particle size 0.5 are printed in cubic feet. The printout shows the sampled quantity of air as 1.000 cfm.
5.9.2 Convert particle count obtained in cubic feet to the particle in cubic meter by multiplying with factor 35.31.
5.10 Calculate for mean, standard deviation and 95% upper confidence limit, as follows
5.10.1 Computation of average particle concentration at a location (P)
          ( T1 + T2 + ……… + TX )
P = -----------------------------------
                               X
Where,
P: Average particle concentration at one location
T1 to TX: Particle concentration of individual samples
X: Number of samples taken at the location
5.10.2 Computation of mean of the averages ( M )
          ( P1 + P2 + ……… + PY )
M = ----------------------------------
                               Y
Where,
M: Mean of averages
P1 to PY: individual location averages
Y: Number of individual location averages
5.10.3 Computation of standard deviation of the mean ( SD )
             (P1 – M) 2 + (P2 – M) 2 + …….. + (PY – M )2
SD = √ ----------------------------------------------------
                                      ( Y – 1 )
Where,
SD : Standard deviation of the mean
5.10.4 Computation of 95% upper confidence limit ( UCL )
                                    SD
95% UCL = M + ( t X ------)
                                    √Y
Where t factor for 95% upper confidence limit is as given in table
Number of individual averages ( Y )
2
3
4
5
6
7- 9
t
6.3
2.9
2.4
2.1
2.0
1.9
5.11 If the 95% UCL value exceeds the class limit, take the count at additional evenly distributed locations and compute the 95% UCL for all locations which should not exceed the desired class limit.
5.12 When only a single location is sampled or when more than nine are sampled computing the mean, standard deviation and 95 % upper confidence limit is not applicable.

5.13 The frequency for taking the particle count
5.13.1 For clean rooms, corridors and process equipment shall be once in six months.
5.13.2 For laminar air flow shall be once in six months.
5.13.3 The particle count testing shall be carried out as per schedule.
5.14 Acceptance Criteria
5.15.1 The cumulative particle concentration for the area should not exceed the desired class limit as given below
Specified By
Class
0.5μ
5.0μ
Cubic meter
Cubic feet
Cubic meter
Cubic feet

ISO 14644
Class - 5
3,520
100
29
0
Class - 7
3,52,000
10,000
2,930
70
Class - 8
35,20,000
1,00,000
29,300
700

In - house
100
3,500
100
0
0
10,000
3,50,000
10,000
2,000
57.14
1,00,000
35,00,000
1,00,000
20,000
571.43
5.15.2 The 95% UCL of particle concentration for the area should not exceed the desired class limit.
5.15 Process equipment having air handling unit shall meet the Class 10,000 requirements.
5.16 The particle count should meet the In-house specified limits.

6.0 ABBREVIATION

6.1 SOP: Standard Operating Procedure
Also see: HVAC System Validation Tests
Get ready to use editable documents in MS-Word FormatView List





Ankur Choudhary is India's first professional pharmaceutical blogger, author and founder of pharmaguideline.com, a widely-read pharmaceutical blog since 2008. Sign-up for the free email updates for your daily dose of pharmaceutical tips.
.moc.enilediugamrahp@ofni :liamENeed Help: Ask Question


No comments:

Post a Comment

Please don't spam. Comments having links would not be published.


Popular Categories

QA SOPs QC SOPs Micro SOPs HVAC Production SOPs Stores SOPs Checklists Maintenance SOPs HPLC Sterile GLP Validation Protocols Water System GDP Regulatory Maintenance Calibration Warning Letters Education B.Pharmacy
Online Courses


Follow Pharmaguideline


DOCUMENTS

PHARMACEUTICAL DOCUMENTS




Editable Pharmaceutical Documents in MS-Word Format. Ready to use SOPs, Protocols, Master Plans, Manuals and more...

View


adsbypg


Recent Posts