1.0 OBJECTIVE
To lay down the procedure for sanitization of purified water generation system using hot water.2.0 SCOPE
This SOP shall be applicable for purified water generation system comprising of Micron Cartridge Filter (MCF), Ultra Filtration (UF) system in utility block.3.0 RESPONSIBILITY
Operator/Engineer/Executive4.0 ACCOUNTABILITY
Head of Engineering5.0 PROCEDURE
5.1 Hot water sanitization for MCF and UF system to be carried out by using hot water sanitization skid in the following manner.5.2 Collect 100 liters of purified water in hot water sanitization skid tank.
5.3 Stop the purified water generation plant (UF).
5.4 Connect flexible stainless steel hose pipes from hot water sanitization skid to MCF inlet and UF recirculation outlet back to hot water skid tank.
5.5 Start the skid pump to circulate water.
5.6 Turn the water heater ‘ON’.
5.7 Adjust the skid pump discharge valve to maintain the system pressure 50-60 psi.
5.8 Initially circulate water at ambient temperature. Gradually increase the water temperature during circulation to 80ºC ±2º C.
5.9 After the temperature reaches 80ºC ±2ºC, continue recirculation for minimum 1 hour.
5.10 During hot water recirculation keep all sampling valves, drain valves and all sensors inlet valves slightly open for 10 minutes.
5.11 Re-circulate the hot water from MCF outlet to recirculation outlet back to hot water skid tank for 15-20 minutes.
5.12 After sanitization is completed, turn ‘off’ the water heater and skid pump.
5.13 Drain about ½ the volume of water from the tank.
5.14 Restart the skid pump.
5.15 Gradually add purified water to the skid tank, while recirculating water through the system until the temperature of recirculating water reaches appox. 40ºC.
5.16 Disconnect the hot water sanitization skid from MCF inlet and UF recirculation outlet.
5.17 Start the purified water generation plant (UF).
5.18 Document the sanitization activity
5.19 Frequency once a week.
Related: Sanitization of RO Membranes in Purified Water System
6.0 ABBREVIATIONS
6.1 SOP: Standard Operating Procedure6.2 MCF: Micron Cartridge Filter
6.3 UF: Ultra Filtration
Also see: Removal of Pathogenic Bacteria from Water System